Application Note · Harmonic Standard
IEEE Standard 519-2022Update & changes from its predecessor 2014

IEEE 519 – 2022 What Is Changed From IEEE-519-2014

A power-quality application note from Foretec Electric India Pvt Ltd, examining the changes the 2022 revision introduces over the 2014 edition — current-distortion sources, even-order harmonic limits, and the calculation of IL.

Voltage & current · 50 Hz
Voltage (sine) Current (harmonic distortion)
Current follows the voltage and jumps in harmonic steps · 5ᵗʰ + 7ᵗʰ + 11ᵗʰ + 13ᵗʰ
Standard
IEEE 519-2022
Supersedes
IEEE 519-2014
Subject
Harmonic control
Date
20ᵗʰ October 2022
Introduction

Update and changes from its predecessor 2014

IEEE-519 is an often-referenced standard that prescribes recommendations for Harmonic Control in Electrical Power Systems. The 2014 version of this recommendation has been adopted internationally for harmonics mitigation by the Regulatory Authorities, including the Central Electricity Authority of India, for framing rules so that the Regulatory Commission issues directions to the Electricity Supply Companies for implementation. This Standard has been revised, and IEEE 519-2022 has come into existence. The changes in the new standards address the important issues relating to the areas like measurement, treating equipment like grid-interactive inverters, etc., as current producing ones for harmonic compliance, besides salient other issues for improving power quality in the power system. Various changes made in the new standards are discussed in this paper to enable the stakeholders to understand the true nature of the equipment for harmonic compliance during selection so that the challenges in providing harmonics filters later are minimised.

Current Distortion SourcesClause 1.2 · Clause 5.2

Current distortion sources

In clause 1.2- “Purpose” of this standard, the word “passive” has been removed to imply that any equipment addition by the user results in altering the impedance characteristic that increases voltage distortions, shall come under the purview of this standard. IEE519-2014 does not prescribe specific guidelines for installations involving distributed energy generation or Invertor based grid interactive equipments or any other form of such equipment that becomes a current producing source.

As per changes made in the new standards under clause 5.2, when an installation like solar power is connected to inverter-based sources to the grid with generation exceeding 10% of the annual average demand, the current harmonics limits specified in IEEE1547 or IEEE2800 need to be followed. The decision tree below explains the compliance with the harmonics limits in the case of Inverter-based Resources.

Decision Tree Harmonic-limit compliance · Inverter-based Resources
Start Does the installation have DER or IBR? No IEEE 519 current limits at PCC will be applied Yes Is the rated generation <10% of annual average load demand? Yes IEEE 519 current limits at PCC will be applied No Current limits acc. to IEEE 1547 or IEEE 2800 will be applied
Fig. — Compliance decision tree for harmonic limits in the case of Inverter-based Resources (IBR), per clause 5.2.
Even Order HarmonicsEnhanced limits

Even order harmonics

In the new standards, the limits for the even order current harmonics are enhanced. The relaxation offered by such enhanced limits is twice the limits prescribed in the earlier standards for the harmonics order of <=6 and the relaxation offered by such enhanced limits is four times the limits prescribed in the earlier standards for the harmonics order of >6.

On power systems, even-order harmonics are undesirable, and their occurrence could signify an imbalance between the waveform's positive and negative sides. The more IBR, AFE drive, and active filters there are, the more likely it is that some levels of even-order harmonics may not always comply with the stricter individual and, especially, even-order harmonic limitations in the earlier 2014 standard, leading to the perception that these enhanced limits are necessary. Table 2 and 3 of IEEE-510-2022 is furnished below for reference:

Table 2Current distortion limits for systems rated 120 V through 69 kV
Maximum harmonic current distortion in percent of IL
Individual harmonic orderb
Isc/IL 2 ≤ h < 11a 11 ≤ h < 17 17 ≤ h < 23 23 ≤ h < 35 35 ≤ h ≤ 50 TDD
< 20c4.02.01.50.60.35.0
20 < 507.03.52.51.00.58.0
50 < 10010.04.54.01.50.712.0
100 < 100012.05.55.02.01.015.0
> 100015.07.06.02.51.420.0
a For h ≤ 6, even harmonics are limited to 50% of the harmonic limits shown in the table.
Table 3Current distortion limits for systems rated above 69 kV through 161 kV
Maximum harmonic current distortion in percent of IL
Individual harmonic orderb
Isc/IL 2 ≤ h < 11a 11 ≤ h < 17 17 ≤ h < 23 23 ≤ h < 35 35 ≤ h ≤ 50 TDD
< 20c2.01.00.750.30.152.5
20 < 503.51.751.250.50.254.0
50 < 1005.02.252.00.750.356.0
100 < 10006.02.752.51.00.57.5
> 10007.53.53.01.250.710.0
a For h ≤ 6, even harmonics are limited to 50% of the harmonic limits shown in the table.
Calculation of ILClause 3.1

Calculation of IL (Average Demand Load current)

In the 2014 edition, one of the points of contention is the calculation of IL when the installation does not have the previous 12 months' demand current. The ambiguity in calculating IL is eliminated in the IEEE519-2022 as per clause 3.1, which is reproduced below:

IEEE 519-2022 · Clause 3.1 — reproduced

This current value is established at the point of common coupling and shall be taken as the sum of the RMS currents corresponding to the 15 min or 30 min maximum demand during each of the twelve previous months divided by 12. If 12 months of data is not available due to the length of time in service, then the maximum 15 min or 30 min apparent power demand for each month should be summed over the total number of months available, and then divided by the number of months. For situations where the installation is a proposed new installation, the maximum demand load current shall be based on the projected 15 min or 30 min maximum monthly apparent power demand over the course of the year following operation of the proposed harmonic producing loads listed on the service application.

Typical CalculationPermissible current harmonics limits

Typical calculation for arriving at the permissible current harmonics limits

Single Line Diagram Substation → PCC → LV side · sample feeder
SubStation 11 Kv Bus / FL - 92 mVA 7/4.09 ACSR Conductor Length 1.85 km R 0.395/km · X /km 7/2.36 ACSR Conductor Length 3.078 km R 1.1850/km · X /km M PCC / Utility Metering point Transformer LV Side
Parameters
ParametersValue
Sanction Max. Demand570 kVA
Average MD for the last 12 Months445 kVA
FL @ PCC24.16 mVA
Isc @ PCC1.27 kA
Isc/IL @ PCC54.37
TDD Limits that apply to this consumer
12
% TDD
Fig. — Sample single line diagram with feeder data, PCC / Utility metering point, and the resulting TDD limit applicable to the consumer.
Tips for ComplianceAction points

Tips for compliance and action points

It is the TDD that determines the limit of harmonic injection and not the iTHD as per standards and regulations. But the TDD variation is based on the IL and the load current during the measurement. The consumer must therefore anticipate a scenario where the load current during the measurement period could be very low compared to the sanctioned demand and plan accordingly to avoid exceeding the limits of harmonics injection into the grid.

Ref : PQWC's white paper - ‘Realities in Harmonic Mitigation
Conclusion

Conclusion

It is, therefore, necessary to observe the following points irrespective of the fact that the new standards are made mandatory by the Regulatory authorities to avoid any embarrassment in the future when statutory implementation comes into effect:

  1. Consumers should understand the true nature of the equipment for harmonic compliance during selection so that the challenges in providing harmonics filters later are minimised.
  2. Monitor Power quality compliance continuously to ensure that the power quality parameters are well within limits.
  3. Ensure to get the automated results/reports without doing any calculations or manual intervention so that the measurements are not disputed.
  4. Deploying CLASS A Ed3 Power Quality Analyser offers a correct approach on the above points by
    • ensuring continuous monitoring
    • an easy way of monitoring compliance through the device home page
    • Monitoring all the power quality issues like Sags, Swells, and Transients as per IEC61000-4-30.
About Authors

About Authors

Mr. Appavoo Subbiah
Former Chief Electrical Inspector — Tamilnadu State

Certified Energy Auditor, specialist in Electrical Safety and Power Quality.

Mr. Ravichandran Krishnaswamy
Technical Director — Foretec Electric India Pvt Ltd

A veteran in the field of Power Quality and serving customers providing valuable innovative solutions in the working region. With over 30 Years of experience in Power Quality and Energy Management has executed innumerable projects for his customers.

Mr. Hari Balasubramanian
Techno-commercial Executive

A professional Techno commercial executive who served customers in the Middle East and India with a consultative approach. With over 30 Years of work experience had provided customers with unique experiences and delight.

Web www.foretecelectric.com E-mail ravi@foretecelectric.com Date — 20th October 2022
Ref : PQWC's white paper - ‘Realities in Harmonic Mitigation’

Foretec Electric disclaims any responsibility for the accuracy of the material in this article. It is not meant to be taken as legal advice, and we accept no liability for the results that may result from the reader interpreting it in that way.